Medical Office Buildout

submittal review  โ€ข  J. Dickson, PE  โ€ข  2026-06-09
Revise and Resubmit
Revise and Resubmit
Corrections required โ€” resubmit
Submittal 23 07 00-001 for HVAC ductwork insulation proposes ThermaSeal TS-200 (R-6.0). Spec section 23 07 00 para 2.3 requires R-8.0 minimum on concealed supply ductwork. The submittal does not meet the specified R-value and omits the fire-stopping detail at rated-wall penetrations.
Requirements
4
Conflicts
3
Action Items
3
Compliance
60%
3/5 checks

Compliance Checklist

โœ“ASTM E84 flame/smoke ratings provided โ€” compliant
โœ—R-value meets spec minimum โ€” FAILS (R-6.0 vs R-8.0)
โœ—Fire-stopping detail at penetrations โ€” missing
โœ“Manufacturer product data included โ€” compliant
โœ“Installer qualifications listed โ€” compliant

Potential Conflicts

CRITICAL
Proposed R-6.0 is below the specified R-8.0 minimum โ€” non-compliant
REVIEW
No fire-stopping detail provided for duct penetrations at rated walls
REVIEW
Product data does not confirm FSK facing on all runs
Key Requirements
Action Items
UrgencyAction ItemOwner
HighResubmit with R-8.0 product meeting ยง2.3ACME Mechanical
HighProvide UL fire-stopping detail for rated-wall penetrationsACME Mechanical
MediumConfirm FSK facing on concealed runsACME Mechanical
Cross-Reference Diagram
THIS DOC submittal Spec 23 07 00 ยง2.3RFI-042Drawing M-301UL System W-L-2078ASTM E84
Reviewer Notes
Disposition: Revise and Resubmit. The R-value deficiency is the controlling issue; resubmit with a compliant R-8.0 product and include the fire-stopping detail before fabrication.